ADV CONTROL 8-32A 110-240V
Special Price
IDR1,997,820.00
IDR1,997,820.00
Regular Price
IDR6,442,650.00
Out of stock
SKU
LUCB32FU
PRE ORDER
Duration Pre-Order : 60
Duration Pre-Order : 60
TeSys U control and diagnostic unit to be inserted in advanced power bases LUB320, LUB380, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 15kW@400V. It provides full protection to motors with a rated current Ir 8-32A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). It provides a thermal overload alarm to be used locally using a LUFDA module or remotely using a LULC module, and a test push button for overload simulation. To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
| SKU | LUCB32FU |
|---|---|
| range of product | TeSys U |
| product or component type | advanced control unit |
| range | TeSys |
| device application | motor control, motor protection |
| device short name | LUCB |
| [Uc] control circuit voltage | 110...220 V DC, 110...240 V AC |
| utilisation category | AC-41, AC-43, AC-44 |
| [Ue] rated operational voltage | 690 V AC |
| product name | TeSys U |
| product compatibility | power base LUB32, power base LUB320, power base LUB38, power base LUB380, reversing contactor breaker LU2B32FU, reversing contactor breaker LU2B38FU |
| motor power kW | 15 kW at 400...440 V AC 50/60 Hz, 15 kW at 500 V AC 50/60 Hz, 18.5 kW at 690 V AC 50/60 Hz |
| thermal protection adjustment range | 8-32 A |
| thermal overload class | class 10 - frequency limit: 40-60 Hz - temperature compensation: -25-70 °C conforming to IEC 60947-6-2, class 10 - frequency limit: 40-60 Hz - temperature compensation: -25-70 °C conforming to UL 508 |
| function available | earth fault protection, manual reset, protection against overload and short-circuit, protection against phase failure and phase imbalance |
| tripping threshold | 14.2 x Ir +/- 20 % |
| phase failure sensitivity | yes |
| product specific application | basic protection and advanced functions, communication |
| network frequency | 40...60 Hz |
| load type | 3-phase motor - cooling: self-cooled |