Motor Breaker GV4LE Mag 50A 50kA Elink
Special Price
IDR2,032,800.00
IDR2,032,800.00
Regular Price
IDR3,597,790.00
In stock
SKU
GV4LE50N
PRE ORDER
Duration Pre-Order : 60
Duration Pre-Order : 60
TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for protection of 3-phase motors 11-22kW@400V. It provides magnetic protection, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Magnetic protection adjustable by dial, setting range 6-14 In. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). To be used in association with a class 10 or 20 thermal overload relay to complete motor protection. Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
| SKU | GV4LE50N |
|---|---|
| product or component type | circuit breaker |
| range | TeSys |
| device application | motor protection |
| device short name | GV4L |
| control type | toggle |
| [Ics] rated service breaking capacity | 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, 2 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2, 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [In] rated current | 50 A |
| product name | TeSys GV4 |
| utilisation category | category A |
| breaking capacity | Icu 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2, Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, Icu 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2, Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, Icu 8 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| poles description | 3P |
| protection type | short-circuit |
| trip unit technology | electronic, magnetic |
| trip unit rating | 300-700 A |
Write Your Own Review